5.12 Pb Group Swing Frequency, Fixed Length, and Counting

5.12 Pb Group Swing Frequency, Fixed Length, and Counting

ℹ️
Inverter Parameter Attribute Explanation
✅: Indicates that the setting value of this parameter can be changed when the inverter is in both stop and running states;
✳️: Indicates that the setting value of this parameter cannot be changed when the inverter is in a running state;
❎: Indicates that the value of this parameter is an actual detection record value and cannot be changed.

Pb Group: Swing Frequency, Fixed Length, and Counting

Function Code Name Setting Range Factory Value Attribute DEC Address
Pb-00 Swing Frequency Setting Method 0: Relative to Center Frequency
1: Relative to Maximum Frequency
0 ✅ 64256
Pb-01 Swing Amplitude 0.0~100.0% 0.0% ✅ 64257
Pb-02 Jump Frequency Amplitude 0.0~50.0% 0.0% ✅ 64258
Pb-03 Swing Frequency Period 0.1~3000.0s 10.0s ✅ 64259
Pb-04 Rise Time of Swing Triangle Wave 0.1~100.0% 50.0% ✅ 64260
Pb-05 Set Length 0~65535m 1000m ✅ 64261
Pb-06 Actual Length 0~65535m 0m ✅ 64262
Pb-07 Pulses per Meter 0.1~6553.5 100.0 ✅ 64263
Pb-08 Set Count Value 1~65535 1000 ✅ 64264
Pb-09 Specified Count Value 1~65535 1000 ✅ 64265